- ICEA S-75-381/NEMA WC 58
- ASTM B 172
- ASTM B 33
- CAN/CSA-C22.2 No.96

1. Ground check conductor
2. Ground check insulation
3. Power conductor
4. Conductor screen
5. Power core insulation
6. Power core insulation screen
7. Metal/fiber braided layer
8. Grounded conductor
9. Inner sheath
10. Metal/fiber braided layer enforced
11. Outer sheath

SHD-GC-8kV(2AWG~4/0AWG)
Construction |
Number of Strands |
Grounding Conductor Size |
Ground Check Conductor Size |
Nominal Insulation Thickness |
Nominal Jacket Thickness |
Nominal Overall Diameter |
Nominal Weight |
Ampacity |
||||
No of Cores x AWG/kcmil |
- |
AWG/kcmil |
AWG/kcmil |
inch |
mm |
inch |
mm |
inch |
mm |
Ibs/kft |
Kg/km |
A |
3×4 |
259 |
8 |
8 |
0.150 |
3.8 |
0.205 |
5.2 |
1.94 |
49.3 |
2308 |
3594 |
122 |
3×2 |
259 |
6 |
8 |
0.150 |
3.8 |
0.220 |
5.6 |
2.12 |
53.8 |
2920 |
4554 |
159 |
3×1 |
329 |
5 |
8 |
0.150 |
3.8 |
0.220 |
5.6 |
2.21 |
56.1 |
3292 |
5104 |
184 |
3×1/0 |
259 |
4 |
8 |
0.150 |
3.8 |
0.220 |
5.6 |
2.32 |
58.9 |
3675 |
5700 |
211 |
3×2/0 |
329 |
3 |
8 |
0.150 |
3.8 |
0.235 |
6.0 |
2.46 |
62.5 |
4304 |
6593 |
243 |
3×3/0 |
413 |
2 |
8 |
0.150 |
3.8 |
0.250 |
6.4 |
2.62 |
66.5 |
5200 |
7738 |
279 |
3×4/0 |
532 |
1 |
8 |
0.150 |
3.8 |
0.250 |
6.4 |
2.75 |
69.8 |
5840 |
8713 |
321 |
3×250 |
608 |
1/0 |
6 |
0.150 |
3.8 |
0.250 |
6.4 |
2.89 |
73.4 |
6774 |
9948 |
355 |
3×300 |
741 |
1/0 |
6 |
0.150 |
3.8 |
0.265 |
6.7 |
3.04 |
77.2 |
7423 |
11384 |
398 |
3×350 |
888 |
2/0 |
6 |
0.150 |
3.8 |
0.280 |
7.1 |
3.21 |
81.3 |
8543 |
12739 |
435 |
3×500 |
1221 |
4/0 |
6 |
0.150 |
3.8 |
0.295 |
7.5 |
3.56 |
90.4 |
11260 |
16757 |
536 |
*we also supply the rated voltage 15kV and 25kV cables based on customer required