- ICEA S-75-381/NEMA WC 58
- ASTM B 172
- ASTM B 33
- CAN/CSA C22.2 No. 96



- Stranded Tinned Copper Conductor
- EPR Insulation
- Reinforced CPE Jacket
- Conductors: Stranded annealed tinned copper conductor.
- Insulation: EPR.
- Sheath: Reinforced, extra-heavy-duty Chlorinated Polyethylene(CPE), black.
- Other sheath materials/colors can be offered as an option.

Other jacket materials/color such as CSP/PCP/NBR/PVC are available upon request.
Two-layer jacket with reinforcing fiber between the two layers can be offered as an option.

- Minimum Bending Radius: 6×OD
- Maximum Operating Temperature: +90℃

Construction |
No. of Strands |
Nominal Insulation Thickness |
Nominal Overall Diameter |
Nominal Weight |
Ampacity |
|||
No. of Cores×AWG/kcmil |
- |
inch |
mm |
inch |
mm |
lbs/kft |
kg/km |
A |
5×8 |
133 |
0.06 |
1.5 |
1.07 |
27.2 |
776 |
1154 |
50 |
5×6 |
133 |
0.06 |
1.5 |
1.24 |
31.5 |
1024 |
1524 |
68 |
5×4 |
259 |
0.06 |
1.5 |
1.36 |
35.2 |
1432 |
2131 |
88 |
5×2 |
259 |
0.06 |
1.5 |
1.56 |
39.8 |
2051 |
3052 |
116 |
5×1 |
259 |
0.06 |
1.5 |
1.85 |
47.1 |
2665 |
3967 |
136 |
5×1/0 |
266 |
0.08 |
2.0 |
1.98 |
50.4 |
3406 |
5069 |
150 |
5×2/0 |
342 |
0.08 |
2.0 |
2.13 |
54.1 |
3596 |
5351 |
172 |
5×3/0 |
418 |
0.08 |
2.0 |
2.27 |
57.6 |
4728 |
7035 |
200 |
5×4/0 |
532 |
0.08 |
2.0 |
2.46 |
62.6 |
5512 |
8203 |
230 |
Ampacity-based on a conductor temperature of 90C and an ambient air temperature of 40C, per ICEA S-75-381.