Single Core,PVC Insulated Annealed Copper Conductors (450/750V)

Строителство
Диригент
Plain annealed circular copper conforming to IEC:228, class 1 and 2 (also available in aluminum conductors sizes 16 to 630 mm2).
Изолация
PVC type 5 to BS:6746 rated 85°C, (PVC type 1 to BS:6746 rated 70°C also available)
Application: Typical applications include building wiring, equipment wiring, switching and distribution installations in conduits above or under plaster
Features: Insulation adheres tightly to conductors yet strips easily, leaving conductor clean. PVC insulation has good electrical properties.

Диригент |
Изолация |
Опаковка |
|||
Cross sectional area Номинална |
Минимален брой of wires |
Дебелина Номинална |
Общ диаметър Прибл |
Нетно тегло Прибл |
B-Box, S-Spool C-Coil, D-Drum |
m m2 |
|
m m |
m m |
кг/км |
m |
1.5 re |
1 |
0.7 |
3.0 |
19 |
50/100 B/S |
1.5 rm |
7 |
0.7 |
3.2 |
19 |
50/100 B/S |
2.5 re |
1 |
0.8 |
3.6 |
30 |
50/100 B/S |
2.5 rm |
7 |
0.8 |
3.8 |
31 |
50/100 B/S |
4 re |
1 |
0.8 |
4.1 |
47 |
50/100 B/S |
4 rm |
7 |
0.8 |
4.3 |
48 |
50/100 B/S |
6 re |
1 |
0.8 |
4.6 |
66 |
50/100 B/S |
6 rm |
7 |
0.8 |
4.9 |
67 |
50/100 B/S |
10 re |
1 |
1.0 |
5.9 |
110 |
50/100 C |
10 rm |
7 |
1.0 |
6.3 |
113 |
50/100 C |
16 rm |
7 |
1.0 |
7.3 |
171 |
50/100 C |
25 rm |
7 |
1.2 |
9.0 |
268 |
50/100 C |
35 rm |
7 |
1.2 |
10.1 |
361 |
1000/2000 D |
50 rm |
19 |
1.4 |
12.0 |
483 |
1000/2000 D |
70 rm |
19 |
1.4 |
13.8 |
680 |
1000/2000 D |
95 rm |
19 |
1.6 |
16.0 |
941 |
1000/2000 D |
120 rm |
37 |
1.6 |
17.6 |
1164 |
1000 D |
150 rm |
37 |
1.8 |
19.7 |
1400 |
1000 D |
185 rm |
37 |
2.0 |
22.0 |
1800 |
1000 D |
240 rm |
61 |
2.2 |
25.0 |
2380 |
1000 D |
300 rm |
61 |
2.4 |
27.7 |
2970 |
500 D |
400 rm |
61 |
2.6 |
31.3 |
3790 |
500 D |
re - circular solid conductor rm - circular stranded conductor
Контролни кабели с PVC изолация и обвивка на проводници 0,6/1kV
Unarmoured Control Cables

Строителство
Conductor:Plain circular solid or stranded copper, per IEC:228, class 1 and 2 - sizes: 1.5 mm2, 2.5 mm2 and 4 mm2
Insulation: Heat resistive PVC type 5 to BS:6746 rated 85°C for continuous operation (PVC type 1 to BS:6746 rated 70°C also available)
Assembly & Filling
For armoured cables
Insulated cores are laid up together and filled with non-hygroscopic material to form compact and circular cable. Armour bedding shall be an extruded layer of PVC which may be an integral part of the filling.
For unarmoured cables
Insulated conductors are laid up together and provided with lapped or extruded inner covering.
Броня
Поцинковани стоманени ленти или кръгли стоманени телове.
Обвивка
PVC type ST2 to IEC:502 colour black. Flame retardant PVC is also available upon request.
Core identification
Black with white printed numbers 1,2,3...etc.
Standard number of cores
7, 12, 19, 24, 30, 37. Different number of cores are available on request
Application: These cables are suitable for use in a broad range of commercial, in industrial and utility applications where maximum performance will be demanded and may be installed indoors, outdoors, underground, ducts (conduits), on trays or ladders.
Low Smoke Fums,Fire Retardant,Halogen Fire Cable - Copper Conductors 0.6/1kV

Строителен диригент
Plain circular or sector stranded copper conductors, per IEC:228 class 1 and 2.
Изолация
XLPE (cross-linked polyethylene) rated 90°C.
Сглобяване
Two, three or four insulated cores are assembled together.
Inner sheath
In single core cables, inner sheath of halogen free compound is applied over insulation. In multicore cables, assembled cores are covered with
inner sheath of halogen free compound.
Броня
For single core cables, a layer of aluminium wires applied helically over inner sheath. For multicore cables, galvanised round steel wires applied helically over inner sheath.
Обвивка
LSF-FR-HF compound, colour black.
Colours for core identification
Single core - red (black colour on request) Two cores - red and black
Three cores - red, yellow and blue
Four cores - red, yellow, blue and black
Features: Cables manufactured with the above construction have a combination of high flame retardancy as well as low smoke and non-halogen acid gas generation. This makes these cables ideal to install in locations such as chemical plants, hospitals, military installations, underground railways, tunnels, etc
Application: These cables are intended for installation on cable trays or in cable ducts.

Awa armoured LSF-FR-HF Cables- Single Core Copper Conductor - XLPE Insulated 0.6/1kV
Диригент |
Изолация |
Брониране |
Outer sheath |
Опаковка |
|||
Cross sectional area Nominal |
Минимален брой жици |
Дебелина Номинална |
Diameter of aluminium wire Номинална |
Дебелина Номинална |
Общ диаметър Прибл |
Нетно тегло прибл x |
Стандартен пакет |
mm² |
мм |
мм |
мм |
мм |
кг/км |
m±5% |
|
50 |
6 |
1.0 |
1.25 |
1.5 |
18.2 |
710 |
1000 |
70 |
12 |
1.1 |
1.25 |
1.5 |
20.2 |
940 |
1000 |
95 |
15 |
1.1 |
1.25 |
1.6 |
22.3 |
1220 |
1000 |
120 |
18 |
1.2 |
1.25 |
1.6 |
24.2 |
1480 |
1000 |
150 |
18 |
1.4 |
1.60 |
1.7 |
27.4 |
1870 |
500 |
185 |
30 |
1.6 |
1.60 |
1.8 |
30.0 |
2280 |
500 |
240 |
34 |
1.7 |
1.60 |
1.8 |
32.8 |
2880 |
500 |
300 |
34 |
1.8 |
1.60 |
1.9 |
35.6 |
3520 |
500 |
400 |
53 |
2.0 |
2.00 |
2.0 |
40.4 |
4520 |
500 |
500 |
53 |
2.2 |
2.00 |
2.1 |
44.2 |
5640 |
500 |
630 |
53 |
2.4 |
2.00 |
2.2 |
48.8 |
7110 |
500 |
RSW Armoured LSF-FR-HF Cables - Multi Core Copper Conductors- XLPE Insulated 0.6/1kV
Диригент |
Изолация |
Брониране |
Outer sheath |
Опаковка |
|||
Площ на напречното сечение Номинална |
Минимален брой жици |
Дебелина Номинална |
Диаметър на алуминиева тел Номинална |
Дебелина Номинална |
Общ диаметър Прибл |
Нетно тегло Прибл |
Стандартен пакет |
mm2 |
мм |
мм |
мм |
мм |
кг/км |
m±5% |
|
2.5 rm |
7 |
0.7 |
1.25 |
1.4 |
14.3 |
500 |
1000 |
4 rm |
7 |
0.7 |
1.25 |
1.4 |
15.4 |
560 |
1000 |
6 rm |
7 |
0.7 |
1.25 |
1.4 |
16.6 |
670 |
1000 |
10 rm |
7 |
0.7 |
1.25 |
1.5 |
18.7 |
850 |
1000 |
16 rm |
6 |
0.7 |
1.25 |
1.5 |
20.0 |
1060 |
1000 |
25 rm |
6 |
0.9 |
1.25 |
1.6 |
24.1 |
1620 |
1000 |
35 rm |
6 |
0.9 |
1.60 |
1.7 |
23.4 |
1930 |
500 |
2.5 rm |
7 |
0.7 |
1.25 |
1.4 |
14.8 |
540 |
1000 |
4 rm |
7 |
0.7 |
1.25 |
1.4 |
16.0 |
620 |
1000 |
6 rm |
7 |
0.7 |
1.25 |
1.4 |
17.3 |
755 |
1000 |
10 rm |
7 |
0.7 |
1.25 |
1.5 |
20.2 |
960 |
1000 |
16 rm |
6 |
0.7 |
1.25 |
1.6 |
21.2 |
1240 |
1000 |
rm - circular stranded conductor sm - sectoral stranded conductor

Едножилен кабел
1. Диригент
- 2. PVC изолация тип 5
3. PVC

Многожилен кабел
1. Диригент
2. PVC изолация
- 3. Екструдирани постелки
- 4. PVC обвивка
Многожилен кабел
- 1. Секторен алуминиев/меден проводник
2. PVC изолация тип 5
3. Централен пълнител
4. Екструдирани постелки
5. Кръгла стоманена тел, бронирана - 6. LSF-FR-HF комбинирана обвивка