8000 Series Aluminium Alloy Conductor SER Service Entrance Cable

 Construction: The stranded compacted 8000 series aluminium alloy conductor is insulated with black XLPE. The insulated conductors are cabled together with AL-alloy concentric neutral and fiberglass reinforced polyester tape binder, and over sheathed by grey sunlight resistant PVC.





PDF Khuphela

Iinkcukacha

Iithegi

 

Iinkcukacha zemveliso

 

Application: Mainly used to convey power from the Service drop to the meter base to the distribution board. SEU can also be used in certain branch circuits as permitted by 1999 NEC. It is used in wet or dry locations.

Rated Voltage:600V.

Ubushushu bokusebenza: Max permissible continuous operating temperature of conductor shall not exceed 90℃.

Umgangatho: UL 44 and UL 854,Federal Specification J-C-30B or other standards required by customers.

Ukupakisha: Steel/wooden reel, wooden reel or steel reel.

 

Imigangatho

 

Aluminum Alloy SEU Service Entrance Cable

Umqhubi

Approx. Overall

Ububanzi

Conductor*

Approx. Overall

Ububanzi

No. of Cores

Size AWG

intshi

No. of Cores

Size AWG

intshi

2

8-2

0.368

3

1/0-1/0-1/0

0.680x1.125

2

6-2

0.430

3

2/0-2/0-2/0

0.736x1.221

2

4-2

0.499

3

3/0-3/0-3/0

0.826x1.358

2

2-2

0.569

3

4/0-4/0-4/0

0.878x1.462

3

8-8-8

0.386x0.600

3(reduced neutral)

4-4-6

0.474x0.775

3

6-6-6

0.430x0.687

3(reduced neutral)

2-2-4

0.554x0.910

3

4-4-4

0.499x0.800

3(reduced neutral)

1/0-1/0-2

0.667x1.101

3

2-2-2

0.569x0.925

3(reduced neutral)

2/0-2/0-1

0.720x1.205

3

1-1-1

0.643x1.051

3(reduced neutral)

4/0-4/0-2/0

0.835x1.419

All values are nominal and subject to correction.