Konduktor Konstruksi
Plain circular or sector stranded copper conductors, per IEC:228 class 1 and 2.
Isolasi
XLPE (cross-linked polyethylene) rated 90°C.
Perakitan
Two, three or four insulated cores are assembled together.
Inner sheath
In single core cables, inner sheath of halogen free compound is applied over insulation. In multicore cables, assembled cores are covered with inner sheath of halogen free compound.
Baja
For single core cables, a layer of aluminium wires applied helically over inner sheath. For multicore cables, galvanised round steel wires applied helically over inner sheath.
Sarung
LSF-FR-HF compound, colour black.
Colours for core identification
Single core - red (black colour on request) Two cores - red and black
Three cores - red, yellow and blue
Four cores - red, yellow, blue and black
Features: Cables manufactured with the above construction have a combination of high flame retardancy as well as low smoke and non-halogen acid gas generation. This makes these cables ideal to install in locations such as chemical plants, hospitals, military installations, underground railways, tunnels, etc
Application: These cables are intended for installation on cable trays or in cable ducts.

Awa armoured LSF-FR-HF Cables- Single Core Copper Conductor - XLPE Insulated 0.6/1kV
Konduktor |
Isolasi |
Armor |
Outer sheath |
Kemasan |
|||
Luas penampang nominal |
Jumlah minimum kabel |
Ketebalan Nominal |
Diameter kawat aluminium Nominal |
Ketebalan Nominal |
Diameter keseluruhan sekitar |
Berat bersih Sekitar x |
Paket standar |
mm² |
mm |
mm |
mm |
mm |
kg/km |
m±5% |
|
50 |
6 |
1.0 |
1.25 |
1.5 |
18.2 |
710 |
1000 |
70 |
12 |
1.1 |
1.25 |
1.5 |
20.2 |
940 |
1000 |
95 |
15 |
1.1 |
1.25 |
1.6 |
22.3 |
1220 |
1000 |
120 |
18 |
1.2 |
1.25 |
1.6 |
24.2 |
1480 |
1000 |
150 |
18 |
1.4 |
1.60 |
1.7 |
27.4 |
1870 |
500 |
185 |
30 |
1.6 |
1.60 |
1.8 |
30.0 |
2280 |
500 |
240 |
34 |
1.7 |
1.60 |
1.8 |
32.8 |
2880 |
500 |
300 |
34 |
1.8 |
1.60 |
1.9 |
35.6 |
3520 |
500 |
400 |
53 |
2.0 |
2.00 |
2.0 |
40.4 |
4520 |
500 |
500 |
53 |
2.2 |
2.00 |
2.1 |
44.2 |
5640 |
500 |
630 |
53 |
2.4 |
2.00 |
2.2 |
48.8 |
7110 |
500 |
RSW Armoured LSF-FR-HF Cables - Multi Core Copper Conductors- XLPE Insulated 0.6/1kV
Konduktor |
Isolasi |
Armor |
Outer sheath |
Kemasan |
|||
Luas penampang nominal |
Jumlah minimum kabel |
Ketebalan Nominal |
Diameter kawat aluminium Nominal |
Ketebalan Nominal |
Diameter keseluruhan sekitar |
Berat bersih sekitar |
Paket standar |
mm² |
mm |
mm |
mm |
mm |
kg/km |
m±5% |
|
2.5 rm |
7 |
0.7 |
1.25 |
1.4 |
14.3 |
500 |
1000 |
4 rm |
7 |
0.7 |
1.25 |
1.4 |
15.4 |
560 |
1000 |
6 rm |
7 |
0.7 |
1.25 |
1.4 |
16.6 |
670 |
1000 |
10 rm |
7 |
0.7 |
1.25 |
1.5 |
18.7 |
850 |
1000 |
16 rm |
6 |
0.7 |
1.25 |
1.5 |
20.0 |
1060 |
1000 |
25 rm |
6 |
0.9 |
1.25 |
1.6 |
24.1 |
1620 |
1000 |
35 rm |
6 |
0.9 |
1.60 |
1.7 |
23.4 |
1930 |
500 |
2.5 rm |
7 |
0.7 |
1.25 |
1.4 |
14.8 |
540 |
1000 |
4 rm |
7 |
0.7 |
1.25 |
1.4 |
16.0 |
620 |
1000 |
6 rm |
7 |
0.7 |
1.25 |
1.4 |
17.3 |
755 |
1000 |
10 rm |
7 |
0.7 |
1.25 |
1.5 |
20.2 |
960 |
1000 |
16 rm |
6 |
0.7 |
1.25 |
1.6 |
21.2 |
1240 |
1000 |
25 rm |
6 |
0.9 |
1.60 |
1.7 |
26.7 |
1720 |
500 |
35 sm |
6 |
0.9 |
1.60 |
1.8 |
25.9 |
2130 |
500 |
50 sm |
6 |
1.0 |
1.60 |
1.8 |
28.5 |
2380 |
500 |
70 sm |
12 |
1.1 |
1.60 |
1.9 |
32.2 |
3150 |
500 |
95 sm |
15 |
1.1 |
2.00 |
2.1 |
37.0 |
4320 |
500 |
120 sm |
18 |
1.2 |
2.00 |
2.2 |
40.4 |
5200 |
500 |
150 sm |
18 |
1.4 |
2.50 |
2.3 |
45.5 |
6620 |
500 |
185 sm |
30 |
1.6 |
2.50 |
2.4 |
49.8 |
7980 |
500 |
240 sm |
34 |
1.7 |
2.50 |
2.6 |
55.1 |
9960 |
250 |
300 sm |
34 |
1.8 |
2.50 |
2.7 |
60.2 |
12060 |
250 |
rm - circular stranded conductor sm - sectoral stranded conductor

Kabel Inti Tunggal
1. Konduktor
2. Isolasi PVC Tipe 5
3. Plastik PVC

Kabel Multi-inti
1. Konduktor
2. Isolasi PVC
3. Tempat tidur ekstrusi
4. Selubung PVC
Kabel Multi-inti
1. Konduktor Aluminium/Tembaga Sektoral
2. Isolasi PVC Tipe 5
3. Pengisi Tengah
4. Tempat tidur ekstrusi
5. Kawat Baja Bulat Berlapis Baja
6. Selubung gabungan LSF-FR-HF