It is installed in cable tray and approved raceways. It is suitable for use in wet or dry locations. If it should be directly buried in the earth, MC cable with PVC sheath is an optimal choice. Its Maximum voltage rating for all applications is 600V.

- نومول شوي ولتاژ: 600V.
- The soft annealed solid or stranded copper conductor.
- Insulated with moisture and flame-resistant PVC and covered with a layer of nylon sheath.
- د المونیم الیاژ یو تړل شوی زغره.
- د PVC میان اختیاري دی.
- Meets or exceeds industry requirements of UL 83 and UL 1569 or other standards required by Customers.

THHN/THWN-2 Metal Clad(MC) Cable
Phase Conductor |
بې طرفه |
Diameter (Inches) |
Weight Per 1000 feet (lbs.) |
Allowable Ampacity |
|
Size (AWG) |
Size (AWG) |
Complete Cable |
75℃ |
90℃ |
|
1/3 |
6 Green Insulated |
1.203 |
1137 |
130 |
150 |
1/4 |
6 Green Insulated |
1.351 |
1456 |
130 |
150 |
1/0-3 |
6 bare |
1.245 |
1344 |
150 |
170 |
1/0-4 |
6 bare |
1.362 |
1733 |
150 |
170 |
2/0-3 |
6 bare |
1.339 |
1630 |
175 |
195 |
2/0-4 |
6 bare |
1.491 |
2180 |
175 |
195 |
3/0-3 |
4 bare |
1.449 |
2037 |
200 |
225 |
3/0-4 |
4 bare |
1.615 |
2709 |
200 |
225 |
4/0-3 |
4 bare |
1.570 |
2555 |
230 |
260 |
4/0-4 |
4 bare |
1.749 |
3307 |
230 |
260 |
250-3 |
4 bare |
1.737 |
`2980 |
255 |
290 |
250-4 |
4 bare |
1.913 |
3868 |
255 |
290 |
350-3 |
3 bare |
1.960 |
4029 |
310 |
350 |
350-4 |
3 bare |
2.162 |
5247 |
310 |
350 |
500-3 |
2 bare |
2.238 |
5576 |
380 |
430 |
500-4 |
2 bare |
2.477 |
7289 |
380 |
430 |
600-4 |
2 bare |
2.483 |
8237 |
420 |
475 |
750-3 |
1 bare |
2.675 |
8158 |
475 |
535 |
750-4 |
1 bare |
2.960 |
10692 |
475 |
535 |
All values are nominal and subject to correction.